Multi station — JUNG Mechanisms, Ivory, art. 2570M1SR
Mechanisms · Ivory · 2570M1SR
Mechanisms·2570M1SR

Multi station

Retail Price

658,065

Made to order from Germany

Characteristics

Article number
2570 M1SR
EAN/GTIN
4011377360006
KNX Secure
Secure

Description & specifications

KNX multi station rail mounting device, 4 rail units

Intended use

KNX bus

Product characteristics

Fan coil function

Switching function

Blinds function

Function of valve drives

HVAC function

Dimming function

Satellite units

  • Switching of electrical fan coil units and other eletrical loads for AC 110 / 230 V
  • Switching and dimming of lighting
  • Switching of electrically driven blinds, shutters and awnings
  • Switching of electrothermal valve drives
  • Room thermostat for controlling the temperature
  • Inputs for polling conventional, floating contacts, and transmitting telegrams to the
  • Outputs for controlling LEDs
  • Operation in KNX system
  • Mounting on DIN rail according to EN 60715 in distribution box
  • Outputs can be operated manually
  • Feedback in manual operation and in bus operation
  • Scene function
  • Disabling of individual outputs manually or via bus
  • Operating hours counter, except blind function
  • Switch-off of unnecessary outputs
  • Logic functions
  • KNX Data Secure compatible with ETS 5.7.7 or ETS 6.3.0 or higher
  • Can be updated with the ETS Service App
  • Connection of up to two fan coils with fan levels
  • Operating modes for heating, cooling or combined heating/cooling operations
  • 2-pipe or 4-pipe operation
  • Individual or hierarchical switching of fan levels
  • Operation as 1-way NO or 1-way NC contacts
  • Logic operation and forced guidance
  • Feedback function
  • Central switching function with collective feedback
  • Time functions: switch-on delay, switch-off delay, staircase lighting timer with switch- off warning
  • Suitable for 110 / 230 V AC motors
  • Blind/shutter position directly controllable
  • Slat position directly controllable
  • Feedback of movement status, blind/shutter position and slat position
  • Forced position through higher-level controller
  • Safety function: rain alarm, frost alarm, 3 independent wind alarms
  • Sun protection function
  • Switching operation or PWM operation
  • Valve drives with characteristics "normally open" or "normally closed" can be controlled
  • Overload-protected, short circuit-protected
  • Integrated room temperature control with setpoint specification
  • Controller function for heating and cooling
  • Protection against jamming valves
  • Emergency operation in case of bus voltage failure for summer and winter
  • Forced position
  • Various setpoints for forced position or emergency operation in case of bus failure for summer or winter
  • Cyclical monitoring of the input signals can be parameterised
  • Automatic or manual setting of the dimming principle suitable for the load
  • No-load protection
  • Electronic short-circuit protection
  • Electronic over-temperature protection
  • Signal in the event of a short-circuit, power failure and overload
  • Parameterisable switch-on and dimming behaviour
  • Time functions: switch-on delay, switch-off delay, staircase lighting timer with switch- off warning
  • Power failure longer than approx. 5 seconds causes the dimming outputs to switch off. Depending on the parameter setting, the connected load is calibrated after voltage return.
  • Power extension possible by connecting dimming outputs in parallel
  • Connection of floating contacts, such as push-buttons, switches or reed contacts
  • Polling with a pulsed current avoids contact contamination (formation of an oxide layer) on the connected contacts
  • Operating functions: switching, dimming, blind, scene or room temperature control
  • Value transmitter for dimming, colour temperature, RGBW, temperature or brightness values
  • Transmitting the current input status after bus voltage failure
  • Connection of door or window contacts for evaluation of the open, closed, tilted and handle position statuses
  • Pulse counter with main and intermediate meters
  • Combination of adjacent input channels when connecting push-button, door or window contact
  • Connection of LED e.g. LED lamp, 5 V DC, 2.2 mA (ref-no. 9605 LED ..)
  • Short-circuit proof, overload protected and protected against polarity reversal
  • Parallel switching of outputs possible, for electrical loads with higher current requirements

Technical data

Rated voltage
AC 110/230 V ~
Mains frequency
50/60 Hz
Ambient temperature
−5 ... +45 °C
Storage/transport temperature
−25 ... +70 °C
Power loss
max. 2.4 W
Stand-by power
max. 0.42 W Dimming outputs A1 ... A2
Connected load
see operating instructions Satellite units
Electrothermal valve drives
max. 4 (230 V), 2 (110 V) Relay outputs A3 ... A8
Switching voltage
AC 230 V ~
Switching current
16 A
AX load
16 AX
External ballasts
16 A, 140 μF
Ohmic load
3680 W
Output voltage
DC 5 V SELV
Output current 1 ... 4
max. 3.2 mA
Cable length
max. 30 m
Cable type
J-Y(St)Y 2 x 2 x 0.8 mm
Mounting width
72 mm (4 rail units)
KNX medium
TP 256
Commissioning mode
S-mode
Rated voltage KNX
DC 21 ... 32 V SELV
Current consumption KNX
12 ... 20 mA
Connection, KNX
connection terminal

Technical datasheet

Official JUNG document · PDF · 2570M1SR

Compatible Products

17

Frames, rockers, sockets and covers that fit this article. Filter by colour, range or gang count.

Logistics

Single Item

Packaging unit
1 pc.
Weight
316 G
Length
95 MM
Height
77 MM
Width
96 MM

Carton

Packaging unit
1 pc.
Weight
316 G
Length
95 MM
Height
77 MM
Width
96 MM

Certifications

BPIK_KNX_Secure